Skip to content
Skip to product information
Description
Specifications
Model / Code SLC‑10000‑TWIN RT2 B1
Rated Power (VA / W) 10,000 VA / 10,000 W
Output Power Factor 1.0 (kW = kVA)
Technology On‑line double conversion (VFI)
Format Convertible Tower / Rack
Input Nominal Voltage 220 V / 230 V / 240 V
Input Voltage Range 110 V ÷ 300 V (up to ~50% load)
Input Rated Frequency 50 Hz / 60 Hz (auto‑detection)
Input Frequency Range ±4 Hz
Input THDi (Total Harmonic Distortion Input) ≤ ~4%
Input Power Factor >0.99 at full load
Output Voltage (Nominal) 208 V / 220 V / 230 V / 240 V
Static Output Accuracy ±1%
Output THDv (Linear Load) <1%
Output THDv (Non‑Linear Load) <4%
Efficiency (Online Mode) ~93% – 94%
Eco‑Mode Efficiency ≥99%
Admissible Overload Capability <110% for 10 min; <130% for 1 min; >130% for 1 s
Parallel Operation Capability Up to 3 units in parallel
Battery / Charger Info No internal batteries included (external battery bank required)
Recharge Time ~7‑9 hours to ~90% charge
Operating Temperature 0 °C to +40 °C
Relative Humidity Up to 95% (non‑condensing)
Maximum Operating Altitude Up to ~2,400 m (power degradation above)
Dimensions (W × D × H) ~438 mm (W) × ~630 mm (D) × ~88 mm (H)
Weight ~20 kg
Standards / Certifications Safety: IEC/EN 62040‑1; EMC: IEC/EN 62040‑2 (C3); Operation: VFI‑SS‑11

Salicru 698CC000005 SLC-10000-TWIN RT2 B1 10kVA Online Double-Conversion Tower/Rack UPS Price in Dubai UAE

698CC000005

  • RACK MOUNT
  • ONLINE UPS
  • DOUBLE CONVERSION
Description
Specifications
Model / Code SLC‑10000‑TWIN RT2 B1
Rated Power (VA / W) 10,000 VA / 10,000 W
Output Power Factor 1.0 (kW = kVA)
Technology On‑line double conversion (VFI)
Format Convertible Tower / Rack
Input Nominal Voltage 220 V / 230 V / 240 V
Input Voltage Range 110 V ÷ 300 V (up to ~50% load)
Input Rated Frequency 50 Hz / 60 Hz (auto‑detection)
Input Frequency Range ±4 Hz
Input THDi (Total Harmonic Distortion Input) ≤ ~4%
Input Power Factor >0.99 at full load
Output Voltage (Nominal) 208 V / 220 V / 230 V / 240 V
Static Output Accuracy ±1%
Output THDv (Linear Load) <1%
Output THDv (Non‑Linear Load) <4%
Efficiency (Online Mode) ~93% – 94%
Eco‑Mode Efficiency ≥99%
Admissible Overload Capability <110% for 10 min; <130% for 1 min; >130% for 1 s
Parallel Operation Capability Up to 3 units in parallel
Battery / Charger Info No internal batteries included (external battery bank required)
Recharge Time ~7‑9 hours to ~90% charge
Operating Temperature 0 °C to +40 °C
Relative Humidity Up to 95% (non‑condensing)
Maximum Operating Altitude Up to ~2,400 m (power degradation above)
Dimensions (W × D × H) ~438 mm (W) × ~630 mm (D) × ~88 mm (H)
Weight ~20 kg
Standards / Certifications Safety: IEC/EN 62040‑1; EMC: IEC/EN 62040‑2 (C3); Operation: VFI‑SS‑11
Drawer Title